Application
- Power circuit up to 15KV.
- Fixed installation in both explosion risk and same areas.
- Medium voltage power cables are for use aboard commercial ships, mobile offshore drilling units (MODUs), and fixed or floating offshore facilities.
- Maximum operating conductor temperature 90 °C.
Construction Details
1) Conductor : Soft annealed tinned copper per ASTM B 33 flexible stranding
2) Conductor shield : Semi-conducting tape with extruded semi-conducting compound according to UL 1072 and ICEA S-68-516
3)Insulation : Extruded Ethylene propylene rubber (Type E) according to IEEE 45-1998/1580-2001, UL 1309/1072 & ICEA-S-68-516
4) Individual shield : Extrude semi-conducting compound according to UL 1072 and ICEA S-68-516
5) Metallic braided shield : Tinned copper wire braided shield, 85% minimum coverage.
6) Jacket : Heavy-duty thermosetting Neoprene (Type N) according to IEEE 45-1998/1580-2001, UL 1309/1072 & ICEA S-68-516
7) Armour optional : Basket wave wire armour according to IEEE 45-1998/1580-2001 & UL 1309, bronze, aluminum or tinned copper.
8) Sheath optional: Same as jacket
9) Optional uninsulated grounding conductors sized per UL 1072
Standards Applied
- IEEE 45-1998 / IEEE 1580-2001
- UL 1309
- ICEA S-68-516
- IEEE 1202
- IEC 60332-3 Cat.A
- CSA C22.2 No. 03 : Cold bend -40°C
Cold bend -35°C
Minimum bending radius
· Unarmoured – 6 X O.D.
· Armoured - 8 X O.D.